CROUZET CONTROL
Chronos 2 series timer relays for DIN rail mounting with screw terminal connections and these versions have a 0.7A rated solid state output in a 17.5mm wide housing.
Time range is adjustable (in sub ranges) from 0.1 sec to 100 hours using a selector switch and potentiometer on the front face of the device.
A wide range supply voltage covers most requirements in the standard units.
Some units are single function and some are multi function with the required timing function set by a selector switch on the front face of the device. The available timing functions are defined by a set of letter codes that is common across the whole Crouzet range.
Approvals | CE, Lloyd´s, RoHS, UL |
---|---|
Breaking capacity | 0,7 A |
Cable Area With Sleeve | 2 x 1,5 mm² |
Cable Area Without Sleeve | 2 x 2,5 mm² |
Function | A - Delay on energisation, Ac - Timing after closing and opening of control contact, At - Timing on energisation with memory, B - Timing on impulse (one shot), Bw - Pulse output (adjustable), C - Timing after impulse, D - Symmetrical flashing, Di - Symmetrical flashing, H - Timing on energisation - pulse output, Ht - Delay on energisation with memory |
IP Class Connection | IP20 |
IP Class Front | IP50 |
Mounting | DIN rail |
Multifunction | Yes |
Output | Solid state |
Power Min | 0,01 A |
Repeatability | 0,5 % |
---|---|
Response Closing | 50 ms |
Response From Stroke | 350 ms |
Supply voltage | 24-240V AC |
Switching Current Max | 0,7 A |
Temperature range bearing, from | -30 °C |
Temperature range bearing, to | 60 °C |
Temperature range from | -20 °C |
Temperature range to | 60 °C |
Time Range | 0,1-1s, 1-10s, 6-60s, 1-10min, 6-60min, 1-10h, 10-100h |
Chronos 2 series timer relays for DIN rail mounting with screw terminal connections and these versions have a 0.7A rated solid state output in a 17.5mm wide housing.
Time range is adjustable (in sub ranges) from 0.1 sec to 100 hours using a selector switch and potentiometer on the front face of the device.
A wide range supply voltage covers most requirements in the standard units.
Some units are single function and some are multi function with the required timing function set by a selector switch on the front face of the device. The available timing functions are defined by a set of letter codes that is common across the whole Crouzet range.
|
|
|
|
|
||
---|---|---|---|---|---|---|
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
Articles | Function | Multifunction | Supply voltage | ||
---|---|---|---|---|---|
TIMER MUS2 24-240VAC
Art:
88827004
Copied
|
A - Delay on energisation, Ac - Timing after closing and opening of control contact, At - Timing on energisation with memory, B - Timing on impulse (one shot), Bw - Pulse output (adjustable), C - Timing after impulse, D - Symmetrical flashing, Di - Symmetrical flashing, H - Timing on energisation - pulse output, Ht - Delay on energisation with memory
|
Yes
|
24-240V AC
|
| |
TIMER MAS5 24-240VAC/DC
Art:
88827014
Copied
|
A - Delay on energisation, At - Timing on energisation with memory
|
No
|
24-240V AC/DC
|
| |
TIMER MLS2 24-240VAC
Art:
88827054
Copied
|
L - Asymmetrical flashing, Li - Asymmetrical flashing
|
No
|
24-240V AC
|
|