C-mac® module type RP81 is used for load monitoring of 3-phase motors, as the phase angle (cos ) between motor current and -voltage changes in proportion to the mechanical load of the motor. You will see the biggest change in phase angle, if the motor is loaded between 0 and 60% of nominal load, which makes the RP81 suitable for monitoring of V-belts, pumps running dry, etc.
RP81 can be connected directly to motors with nominal current up to 6 A. If the current is bigger, you use a standard current transformer .
Approvals | CE |
---|---|
Depth | 74 mm |
Frequenze | 40-70Hz |
Height | 76 mm |
Materials Cover | Noryl |
Measuring Range | 0,5-6A |
Power supply V AC | 400 V AC |
Temperature range from | -20 °C |
---|---|
Temperature range to | 60 °C |
Time Delay Start | 0-20 s |
Weight | 110 g |
Width | 38 mm |
C-mac® module type RP81 is used for load monitoring of 3-phase motors, as the phase angle (cos ) between motor current and -voltage changes in proportion to the mechanical load of the motor. You will see the biggest change in phase angle, if the motor is loaded between 0 and 60% of nominal load, which makes the RP81 suitable for monitoring of V-belts, pumps running dry, etc.