PULS
The YR40.245 is a redundancy module, which can be used to build redundant systems. The module has one
input and one output and can carry nominal currents up to 40A. The output is equipped with a plug-connector, which allows replacing the power supply or the redundancy module while the system is running (hotswapping).
The novelty of this redundancy module is the utilization of mosfets instead of diodes for the decoupling of the output. This reduces the heat generation and the voltage drop between input and output. The redundancy module does not require an additional auxiliary voltage.
Due to the low power losses, the unit is very slender and only requires 46mm width on the DIN-rail. Large
connection terminals allow for a safe and fast installation. The large international approval package makes this unit suitable for nearly every application.
Input voltage DC | 12-28 V |
---|---|
Input voltage dc min | 8,4 V DC |
Input voltage dc max | 36,4 V DC |
Input current per channel max | 40 A |
Input current at continuous overload or short circuit max | 65 A |
Type Power Supply | Redundancy modules |
Output voltage | 24 V DC |
Output Current | 40 A |
Output current max | 65 A |
Temperature Range Without Derating From | -40 °C |
Temperature Range Without Derating To | 70 °C |
Life span | 134000 h @ 1x 40 A, 24 V DC, 40 °C |
MTBF (IEC 61709) | 6357000 h @ 1x 40 A, 24 V DC, 40 °C |
---|---|
Width | 46 mm |
Height | 124 mm |
Depth | 127 mm |
Weight | 0,34 kg |
Series | Dimension Y |
Approvals | ABS, ATEX, CB, CE, CSA, CSA US, GL, IECEx, UL |
Material Protection | Aluminium |
IP Class | IP20 |
Voltage Drop Over The Semi-Conductor | 150 mV |
The YR40.245 is a redundancy module, which can be used to build redundant systems. The module has one
input and one output and can carry nominal currents up to 40A. The output is equipped with a plug-connector, which allows replacing the power supply or the redundancy module while the system is running (hotswapping).
The novelty of this redundancy module is the utilization of mosfets instead of diodes for the decoupling of the output. This reduces the heat generation and the voltage drop between input and output. The redundancy module does not require an additional auxiliary voltage.
Due to the low power losses, the unit is very slender and only requires 46mm width on the DIN-rail. Large
connection terminals allow for a safe and fast installation. The large international approval package makes this unit suitable for nearly every application.