PULS
Pulse Dimension Q is a series power supply with very high performance. QT40.481 have built primary fuses that make it possible to connect the unit without the need for intermediate fuses up to 32 A (UL) which saves space and money. The efficiency is high over a wide load range, which results in reduced power consumption and longer life regardless of load current. An average efficiency is 94.7% with a peak value of 95.4%.
The power loss at idle is very low, 9.5 W. The bonus power provides 50% extra reserve with retained 48 V dc (30 A) which is an advantage when connected loads have high starting currents and to bridge temporary current peaks. The bonus power is limited to 4 seconds to avoid constant overloading of the power supply and wiring. In addition to the bonus effect leave the unit a very high short-circuit current (ms) that helps to secondary fuses. See technical data for example.
Active transient ensure operation also in very störrik electrical environment, also have QT40.481 active inrush current protection, which means a very low starting current, even if the unit has been in operation for a longer time. Especially useful for redundant / parallel-connected systems.
Simple diagnostics via DC-OK relay that falls on the output voltage deviates more than 10% from the set value, a green LED indicates DC-OK, Red LED indicates overload.
The unit can also be remote controlled for on / off function. Three different installation options available, see the "Technical data". Can be used instead of expensive DC contactors when you need to break up the 48 V side (remote control function has no safety circuit and therefore should not be used in the security context).
Active PFC reduces power consumption, harmonics close to zero, in addition, the power distribution in phases much smoother at power asymmetry.
In parallel, the output voltage to be adjusted to the same value on both units (± 100 mV) in single mode or let the factory settings on the unit apply to all units. After possible. adjustment of the output voltage, the switch in the front moved to the "parallel use". The units are now ready to work in parallel.
We recommend clearance of 40 mm, 20 mm below the unit and 5 mm on the sides.
Bonus power
The power supply has a bonus power that enables high power output with maintained 48 V dc for 4 seconds, which is a big advantage when connected loads have high starting current, e.g. motors. How often you can use the bonus power depends on the application. With the diagram and formula below you can calculate the available repeat time for each application. Bonus power is available as soon as the power supply starts and immediately after a short circuit.
Bonus power | Operating characteristics | |
Po | Nominal load current | |
Ppeak | Peak current | |
To | Time between bonus power | |
Tpeak | Peak current I time | |
Operating cycle | Tpeak/ (Tpeak+To) | |
To= | Tpeak- (operating cycle*Tpeak) / operating cycle | |
E.g. Peak current (Ppeak) is 25A =125 %. Peak time is 3 seconds. Nominal load current (Po) is 15A. 15 A = 75 % of Inom. According to the diagram the operating cycle is about 0.45. To = 3 - (0.45*3) / 0.45=3.6. Maximal repeat time of the bonus power is 3.6 seconds. |
Output characteristics |
Remote control function This function permits outputs to be shut down by means of an external signals from e.g. a control system or button. Shutdown occurs immediately and to restart has a delay of about 350 ms. In a shutdown state the output voltage is below 2 V DC and the power is less than 0.5 W. |
Input voltage range | Wide-range |
---|---|
Number of phases | 3 |
Input voltage AC | 380-480 V |
Input voltage ac min | 323 V AC |
Input voltage ac max | 576 V AC |
Inrush current at 400 V ac typical | 5 A |
Power Factor at 400 V AC, full load. Typical | 0,88 |
Supply Frequency | 50-60 ±6 % |
Power consumption at 400 V ac | 1,65 A |
Type Power Supply | AC-DC |
Output voltage | 48 V DC |
Output voltage min | 48 V DC |
Output voltage max | 54 V DC |
Output Current | 20 A |
Effect | 960 W |
Power Reduction Of 60 To 70 ° C | 24 W/°C |
Ripple. max | 150 mV pp |
Temperature Range Without Derating From | -25 °C |
Temperature Range Without Derating To | 60 °C |
---|---|
Efficiency At 400 V AC. Typical | 94,7 % |
Efficiency At 400 V AC, full load. Typical | 95,4 % |
Lifetime at 400 V ac, full load and +40 ° C | 86000 h |
MTBF (IEC 61709) 400 V ac, max loan, +40 °C | 375000 h |
Width | 110 mm |
Height | 124 mm |
Depth | 127 mm |
Weight | 1,5 kg |
Clamp type | Spring-clamp |
Series | Dimension Q |
Approvals | CB, CE, CSA, GL, UL |
DC relay output | Yes |
Material Protection | Aluminium |
Hold-up time at 400 V AC, full load. Typical. | 25 ms |
IP Class | IP20 |
Active Transient | Yes |
Pulse Dimension Q is a series power supply with very high performance. QT40.481 have built primary fuses that make it possible to connect the unit without the need for intermediate fuses up to 32 A (UL) which saves space and money. The efficiency is high over a wide load range, which results in reduced power consumption and longer life regardless of load current. An average efficiency is 94.7% with a peak value of 95.4%.
The power loss at idle is very low, 9.5 W. The bonus power provides 50% extra reserve with retained 48 V dc (30 A) which is an advantage when connected loads have high starting currents and to bridge temporary current peaks. The bonus power is limited to 4 seconds to avoid constant overloading of the power supply and wiring. In addition to the bonus effect leave the unit a very high short-circuit current (ms) that helps to secondary fuses. See technical data for example.
Active transient ensure operation also in very störrik electrical environment, also have QT40.481 active inrush current protection, which means a very low starting current, even if the unit has been in operation for a longer time. Especially useful for redundant / parallel-connected systems.
Simple diagnostics via DC-OK relay that falls on the output voltage deviates more than 10% from the set value, a green LED indicates DC-OK, Red LED indicates overload.
The unit can also be remote controlled for on / off function. Three different installation options available, see the "Technical data". Can be used instead of expensive DC contactors when you need to break up the 48 V side (remote control function has no safety circuit and therefore should not be used in the security context).
Active PFC reduces power consumption, harmonics close to zero, in addition, the power distribution in phases much smoother at power asymmetry.
In parallel, the output voltage to be adjusted to the same value on both units (± 100 mV) in single mode or let the factory settings on the unit apply to all units. After possible. adjustment of the output voltage, the switch in the front moved to the "parallel use". The units are now ready to work in parallel.
We recommend clearance of 40 mm, 20 mm below the unit and 5 mm on the sides.
Bonus power
The power supply has a bonus power that enables high power output with maintained 48 V dc for 4 seconds, which is a big advantage when connected loads have high starting current, e.g. motors. How often you can use the bonus power depends on the application. With the diagram and formula below you can calculate the available repeat time for each application. Bonus power is available as soon as the power supply starts and immediately after a short circuit.
Bonus power | Operating characteristics | |
Po | Nominal load current | |
Ppeak | Peak current | |
To | Time between bonus power | |
Tpeak | Peak current I time | |
Operating cycle | Tpeak/ (Tpeak+To) | |
To= | Tpeak- (operating cycle*Tpeak) / operating cycle | |
E.g. Peak current (Ppeak) is 25A =125 %. Peak time is 3 seconds. Nominal load current (Po) is 15A. 15 A = 75 % of Inom. According to the diagram the operating cycle is about 0.45. To = 3 - (0.45*3) / 0.45=3.6. Maximal repeat time of the bonus power is 3.6 seconds. |
Output characteristics |
Remote control function This function permits outputs to be shut down by means of an external signals from e.g. a control system or button. Shutdown occurs immediately and to restart has a delay of about 350 ms. In a shutdown state the output voltage is below 2 V DC and the power is less than 0.5 W. |