PULS
Puls Dimension Q is a series of power supplies with very small construction dimensions and many technical advantages.
The unit has low inrush current (even during warm start), active PFC, which provides a power factor close to one, extended temperature range, as well as active protection against mains transients. Furthermore, there is a relay output (DC OK) that falls when the output voltage deviates more than 10% from the set value.
The bonus power provides 50% extra reserve with retained voltage which is an advantage when connected loads have high starting currents. The unit also provides a high short-circuit current that simplifies tripping of secondary fuses. Both the bonus power and short-circuit current is limited to 4 seconds to avoid constant overloading of the power supply and wiring.
High efficiency for long life and low temperature. The power supply can be connected for two-phase operation Within up to +40°C. At higher temperatures, the load current is reduced.
We recommend clearance of 40 mm and 20 mm below the unit and 5 mm on the sides. (15 mm on the sides if adjacent products are a heat source).
Bonus power
The power supply has a bonus power that enables high power output with maintained 48 V dc for 4 seconds, which is a big advantage when connected loads have high starting current, e.g. motors. How often you can use the bonus power depends on the application. With the diagram and formula below you can calculate the available repeat time for each application. Bonus power is available as soon as the power supply starts and immediately after a short circuit
Bonus power | Operating cycle | ||
Po | Nominal load current | ||
Ppeak | Peak current | ||
To | Time between bonus power | ||
Tpeak | Peak current I time | ||
Operating cycle | Tpeak/ (Tpeak+To) | ||
To | Tpeak- (operating cycle*Tpeak) / operating cycle | ||
E.g. 48 V DC power supply Nominal load current (Po) is 7.5 A. Peak current (Ppeak) is 12A=120 %. Peak time is 3 seconds. 7.5 A=75 % of Inom. According to the diagram the operating cycle is 50%. To= 3- (0.5*3) / 0.5=3. Maximum repeat time of the bonus power is 3 seconds. |
Input voltage range | Wide-range |
---|---|
Number of phases | 3 |
Input voltage AC | 380-480 V |
Input voltage ac min | 323 V AC |
Input voltage ac max | 552 V AC |
Inrush current at 400 V ac typical | 3 A |
Power Factor at 400 V AC, full load. Typical | 0,94 |
Supply Frequency | 50-60 ±6 % |
Power consumption at 400 V ac | 0,79 A |
Type Power Supply | AC-DC |
Output voltage | 48 V DC |
Output voltage min | 48 V DC |
Output voltage max | 55 V DC |
Output Current | 10 A |
Effect | 480 W |
Power Reduction Of 60 To 70 ° C | 12 W/°C |
Ripple. max | 100 mV pp |
Temperature Range Without Derating From | -25 °C |
Temperature Range Without Derating To | 60 °C |
---|---|
Efficiency At 400 V AC. Typical | 94,4 % |
Efficiency At 400 V AC, full load. Typical | 95,4 % |
Lifetime at 400 V ac, full load and +40 ° C | 51000 h |
MTBF (IEC 61709) 400 V ac, max loan, +40 °C | 690000 h |
Width | 65 mm |
Height | 124 mm |
Depth | 127 mm |
Weight | 0,87 kg |
Clamp type | Spring-clamp |
Series | Dimension Q |
Approvals | CB, CE, CSA US, cRUus, cULus, GL |
DC relay output | Yes |
Material Protection | Aluminium |
Hold-up time at 400 V AC, full load. Typical. | 22 ms |
IP Class | IP20 |
Active Transient | Yes |
Puls Dimension Q is a series of power supplies with very small construction dimensions and many technical advantages.
The unit has low inrush current (even during warm start), active PFC, which provides a power factor close to one, extended temperature range, as well as active protection against mains transients. Furthermore, there is a relay output (DC OK) that falls when the output voltage deviates more than 10% from the set value.
The bonus power provides 50% extra reserve with retained voltage which is an advantage when connected loads have high starting currents. The unit also provides a high short-circuit current that simplifies tripping of secondary fuses. Both the bonus power and short-circuit current is limited to 4 seconds to avoid constant overloading of the power supply and wiring.
High efficiency for long life and low temperature. The power supply can be connected for two-phase operation Within up to +40°C. At higher temperatures, the load current is reduced.
We recommend clearance of 40 mm and 20 mm below the unit and 5 mm on the sides. (15 mm on the sides if adjacent products are a heat source).
Bonus power
The power supply has a bonus power that enables high power output with maintained 48 V dc for 4 seconds, which is a big advantage when connected loads have high starting current, e.g. motors. How often you can use the bonus power depends on the application. With the diagram and formula below you can calculate the available repeat time for each application. Bonus power is available as soon as the power supply starts and immediately after a short circuit
Bonus power | Operating cycle | ||
Po | Nominal load current | ||
Ppeak | Peak current | ||
To | Time between bonus power | ||
Tpeak | Peak current I time | ||
Operating cycle | Tpeak/ (Tpeak+To) | ||
To | Tpeak- (operating cycle*Tpeak) / operating cycle | ||
E.g. 48 V DC power supply Nominal load current (Po) is 7.5 A. Peak current (Ppeak) is 12A=120 %. Peak time is 3 seconds. 7.5 A=75 % of Inom. According to the diagram the operating cycle is 50%. To= 3- (0.5*3) / 0.5=3. Maximum repeat time of the bonus power is 3 seconds. |