PULS

Power supply 1-phase, 48 V dc Dimension Q Series

Pulse Dimension Q is a series power supply with very high performance. The efficiency is high over a wide load range, which results in reduced power consumption and longer life regardless of load current. The average efficiency is 94.2% with a peak of 95%. The power loss at idle is only 12 W.

The bonus power provides 50% extra reserve with retained 48 V DC (30 A) which is an advantage when connected loads have high starting currents and to bridge temporary current peaks. The bonus power is limited to 4 seconds to avoid constant overloading of the power supply and wiring. In addition to the bonus effect leave the unit a very high short-circuit current (ms) that helps to secondary fuses. If the overload remains after 4 sec. Ports end in the so called, hiccup mode. When the output voltage drops below 40 V dc shut the unit by the end of the 18's. And then make a new start attempt. If the overload / short connection is gone restarts the power supply automatically. If the overload / short circuit persists, the unit output current of approx. 2 sec and then again turn off.

Heavy transient assure operation even at very störrik electrical environment and also has QS40.484 active inrush current protection, which means a very low starting current, even if the unit has been in operation for a longer time. Especially useful for redundant / parallel-connected systems.

Simple diagnostics via DC-OK relay that falls on the output voltage deviates more than 10% from the set value, a green LED indicates DC-OK, Red LED indicates overload.

The unit can also be remote controlled for on/off function. Three different installation options available, see the "Technical data". Can be used instead of expensive DC contactors when you need to break up the 48 V side (NB. The remote control function has no safety circuit and therefore should not be used in the security context).

Active PFC reduces power consumption, harmonics close to zero and in addition, the power distribution in phases much smoother at power asymmetry.

 

We recommend free space of 40 mm over 20 mm below the unit, as well as 15 mm on the sides.

 

 

Output charcteristic

Remote control function

 

Bonus power

The power supply has a bonus power that enables high power output with maintained 48 V DC for 4 seconds, which is a big advantage when connected loads have high starting current, e.g. motors. How often you can use the bonus power depends on the application. With the diagram and formula below you can calculate the available repeat time for each application. Bonus power is available as soon as the power supply starts and immediately after a short circuit.

 

Bonus power

Operating cycle

Bonus effect diagram power supply QT20.241

Duty cycle diagram power supply QT20.241

Po

Nominal load current

Ppeak

Peak current

To

Time between bonus power

Tpeak

Peak current I time

Operating cycle

Tpeak/(Tpeak+To)

To=

Tpeak-(operating cycle*Tpeak)/operating cycle

E.g. Peak current (Ppeak) is 25A =125 %. Peak time is 3 seconds. Nominal load current (Po) is 15A. 15A =75 % of Inom. According to the diagram the operating cycle is about 0.45. To=3 - (0.45*3) / 0.45=3.6. Maximal repeat time of the bonus power is 3.6 seconds

 

Switching

Function

Overload
LED

DC OK
LED

DC OK
relay contact

Normal operation

Off

On

Closed

During bonus power output

Off

On

Closed

Overload (Hick-up)

Blinks

Off

Open

Short circuit

Blinks

Off

Open

Over temperature

Blinks

Off

Open

Remote shutdown

Blinks

Off

Open

No input voltage

Off

Off

Open

 

Read more
  • Output current of 20 A
  • Up to 95% efficiency
  • High short-circuit currents
  • Maximum performance
  • Remote Function

Selected variant

Selected variant

Specifications

Number of phases 1
Input voltage AC 200-240 V
Input voltage ac min 170 V AC
Input voltage ac max 264 V AC
Inrush current at 230 V ac typical 14 A
Power Factor at 230 V AC, full load. Typical 0,96
Supply Frequency 50-60 ±6 %
Power Consumption At 230 V AC 4,6 A
Type Power Supply AC-DC
Output voltage 48 V DC
Output voltage min 48 V DC
Output voltage max 54 V DC
Output Current 20 A
Effect 960 W
Power Reduction Of 60 To 70 ° C 24 W/°C
Ripple. max 150 mV pp
Temperature Range Without Derating From -25 °C
Temperature Range Without Derating To 60 °C
Efficiency At 230 V AC. Typical 94,2 %
Efficiency At 230 V AC, full load. Typical 95 %
Lifetime at 230 V ac, full load and +40 ° C 65000 h
MTBF (IEC 61709) 230 V AC, Maximum Load, 40 ° C 392000 h
Width 125 mm
Height 124 mm
Depth 127 mm
Weight 1,8 kg
Clamp type Spring-clamp
Series Dimension Q
Approvals ABS, CB, CE, CSA, GL, UL
DC relay output Yes
Material Protection Aluminium
Hold-up time at 230 V AC, full load. Typical. 30 ms
IP Class IP20

Product description

Pulse Dimension Q is a series power supply with very high performance. The efficiency is high over a wide load range, which results in reduced power consumption and longer life regardless of load current. The average efficiency is 94.2% with a peak of 95%. The power loss at idle is only 12 W.

The bonus power provides 50% extra reserve with retained 48 V DC (30 A) which is an advantage when connected loads have high starting currents and to bridge temporary current peaks. The bonus power is limited to 4 seconds to avoid constant overloading of the power supply and wiring. In addition to the bonus effect leave the unit a very high short-circuit current (ms) that helps to secondary fuses. If the overload remains after 4 sec. Ports end in the so called, hiccup mode. When the output voltage drops below 40 V dc shut the unit by the end of the 18's. And then make a new start attempt. If the overload / short connection is gone restarts the power supply automatically. If the overload / short circuit persists, the unit output current of approx. 2 sec and then again turn off.

Heavy transient assure operation even at very störrik electrical environment and also has QS40.484 active inrush current protection, which means a very low starting current, even if the unit has been in operation for a longer time. Especially useful for redundant / parallel-connected systems.

Simple diagnostics via DC-OK relay that falls on the output voltage deviates more than 10% from the set value, a green LED indicates DC-OK, Red LED indicates overload.

The unit can also be remote controlled for on/off function. Three different installation options available, see the "Technical data". Can be used instead of expensive DC contactors when you need to break up the 48 V side (NB. The remote control function has no safety circuit and therefore should not be used in the security context).

Active PFC reduces power consumption, harmonics close to zero and in addition, the power distribution in phases much smoother at power asymmetry.

 

We recommend free space of 40 mm over 20 mm below the unit, as well as 15 mm on the sides.

 

 

Output charcteristic

Remote control function

 

Bonus power

The power supply has a bonus power that enables high power output with maintained 48 V DC for 4 seconds, which is a big advantage when connected loads have high starting current, e.g. motors. How often you can use the bonus power depends on the application. With the diagram and formula below you can calculate the available repeat time for each application. Bonus power is available as soon as the power supply starts and immediately after a short circuit.

 

Bonus power

Operating cycle

Bonus effect diagram power supply QT20.241

Duty cycle diagram power supply QT20.241

Po

Nominal load current

Ppeak

Peak current

To

Time between bonus power

Tpeak

Peak current I time

Operating cycle

Tpeak/(Tpeak+To)

To=

Tpeak-(operating cycle*Tpeak)/operating cycle

E.g. Peak current (Ppeak) is 25A =125 %. Peak time is 3 seconds. Nominal load current (Po) is 15A. 15A =75 % of Inom. According to the diagram the operating cycle is about 0.45. To=3 - (0.45*3) / 0.45=3.6. Maximal repeat time of the bonus power is 3.6 seconds

 

Switching

Function

Overload
LED

DC OK
LED

DC OK
relay contact

Normal operation

Off

On

Closed

During bonus power output

Off

On

Closed

Overload (Hick-up)

Blinks

Off

Open

Short circuit

Blinks

Off

Open

Over temperature

Blinks

Off

Open

Remote shutdown

Blinks

Off

Open

No input voltage

Off

Off

Open

 

Accessories

Related products

Articles Output voltage Input voltage AC Clamp type Effect Output Current
48 V DC
200-240 V
Spring-clamp
960 W
20 A
48 V DC
100-240 V
Spring-clamp
960 W
20 A

Selected variant

Select a variant in the list

Contact us
Please contact us for more information.
Send e-mail
Do you need help?
Logo

Cookies on oem.ee

Cookies help us improve your experience with us, so in order to be able to handle login information, offer you personalised content and for basic functionality of this website, we use some cookies.

Functional cookies

These cookies are necessary for the website to work and can not be turned off in our systems. They are usually used only in response to actions you have taken in connection with a service request, for example when setting personal preferences, logging in or filling out a form.

Analytics cookies

These cookies allow us to count the number of visits and traffic sources so that we can measure and improve our website performance. They help us know which pages are more or less popular and how visitors navigate around the site. The information that these cookies collect is aggregated and therefore completely anonymous. If you do not allow these cookies, we do not know when you have visited our website.

Marketing cookies

These cookies can be added by our partners. They can use them to create a profile of you, based on your interests, to show you more relevant information. They do not store any personal information - only information about your browser and device. If you do not accept these cookies, you will have a more general and less customized user experience.