PULS

Power supply 1-phase, 48 V dc Dimension C Series, Generation 2

Puls Dimension C-series stands for cost optimization without compromising quality, reliability or performance.

CP10 is the second generation C-series 1-phase that sets new records by using the latest technology and sophisticated thermal design. With an efficiency of 95.5%, the power losses are very small and thus the width is reduced down to 39 mm. The efficiency is also very high at lower loads which is the normal operating condition. The mean value is on the whole 94.5% at 230 V ac.

Power boost of 20% enables higher current extraction without voltage drops. This is especially useful during start-ups and to bridge the current peaks in the application. The power reserve can be used continuously up to + 45°C and short periods from +45 to +60°C.

Short-circuit currents. CP10 can provide short circuit current which is 3 times the nominal current for at least 12 ms, which helps secondary fuses and achieve selectivity. For more information see under Sec, fuses.

Hiccup Plus

With Puls new short circuit technology ensures optimum protection. The unit leaves a very high short circuit that solves secondary fuses and provide sufficient starting current for example dc motors. If the output voltage falls below 26 V dc, a continuous current of 7 A is given for 2 seconds, then turn the assembly of the end to make a new restart attempt after about 18 seconds. This is done until the error has been corrected. This feature ensures a high short-circuit/overload current while avoiding a constant high current that can lead to thermal problems with cables and component damage.

More technical advantages. CP10 has active power factor correction (PFC) and actively current inrush protection that effectively reduces start currents which are ideal if several units are connected in the same phase or if the supply is current limited through example. AC UPS. The protection is always active, regardless of the temperature. DC-OK output, wide temperature range, a large number of approvals and transient filter which ensures operation in störrik electrical environment makes the unit suitable for virtually all installations.

 
For good cooling, we recommend a clearance of 40 mm over 20 mm below. We recommend 5 mm air gap to the sides. (15 mm on the sides of adjacent product is a heat source.)

 

Wiring

A: Primary side/control voltage

 

B: Secondary side. Output voltage

 

C: Potentiometer adjustable output voltage 48-56 V dc

 

D: DC OK LED. Lights when the voltage is 90% of the set value

 

E: DC-OK relay output. Closes when the output voltage is OK.

 

 

 

Sec. fuses

Breakers is the most common type of fuse for ac voltage but is also used for dc voltages. Power supply always has a current limitation compared with an electricity network which hampers tripping of a circuit breaker of the magnetic field. Greater consideration must be given to the cable diameter and cable lengths. This even if the power supply is able to deliver high short circuit currents. For long cables and/or thin cable area so the solution is electronic fuses.

 

Puls CP10.481 have high short-circuit currents which enables tripping within 10 ms of length and cable section is as below specification.

 

Safe tripping of breakers with different
cable lengths / diameters

Short circuit. Fig 3-2

 

0.75 mm2

1.0 mm2

1.5 mm2

2.5 mm2

C-2A

42 m

49 m

59 m

109 m

C-3A

13 m

24 m

28 m

42 m

 

 

 

 

Hiccup function. Fig 3-3

 

 

 

 

Description of Hiccupplus function

Thanks to the unique Pul Hiccupplus ensures a high short circuit current while avoiding the risk of overheated cables and damage to the connected loads. When a short circuit occurs following.

  1. High peak power that enables tripping in 12 ms Figure 3-2
  2. The unit leaves 7 A for 2 s.

After 2 seconds the unit shuts off, then try to restart every 18 seconds. If the fault is removed, the unit starts automatically, otherwise it will lose further 18 s. The operation does not burden the cabling and does not cause damage to the electronics.

 

Read more
  • Output current of 5.4 A
  • Up to 95.5% efficiency
  • Active current inrush protection
  • Active PFC
  • Hiccup Plus

Selected variant

Selected variant

Specifications

Input voltage range Wide-range
Number of phases 1
Input voltage AC 100-240 V
Input voltage ac min 85 V AC
Input voltage ac max 264 V AC
Input voltage DC 110-150 V
Input voltage dc min 88 V DC
Input voltage dc max 180 V DC
Inrush current at 120 V ac typical 4 A
Input current at 230 V ac typical 4 A
Power Factor at 120 V AC, full load. Typical 0,98
Power Factor at 230 V AC, full load. Typical 0,91
Supply Frequency 50-60 ±6 %
Power Consumption At 120 V AC 1,09 A
Power Consumption At 230 V AC 0,61 A
Type Power Supply AC-DC
Output voltage 48 V DC
Output voltage min 48 V DC
Output voltage max 56 V DC
Output Current 2,5 A
Effect 120 W
Power Reduction Of 60 To 70 ° C 3 W/°C
Ripple. max 50 mV pp
Temperature Range Without Derating From -25 °C
Temperature Range Without Derating To 60 °C
Efficiency At 120 V AC, full load. Typical 92,6 %
Efficiency At 230 V AC. Typical 91,6 %
Efficiency At 230 V AC, full load. Typical 93,5 %
Lifetime at 120 V ac, full load and +40 ° C 62000 h
Lifetime at 230 V ac, full load and +40 ° C 71000 h
MTBF (IEC 61709) 230 V AC, Maximum Load, 40 ° C 836000 h
Width 32 mm
Height 124 mm
Depth 102 mm
Weight 0,44 kg
Clamp type Screw
Series Dimension C
Approvals ATEX, CB, CE, CSA, IECEx, IEC 62368-1:2018, UL
DC relay output Yes
Material Protection Aluminium
Hold-up time at 120 V AC, full load. Typical. 35 ms
Hold-up time at 230 V AC, full load. Typical. 35 ms
IP Class IP20
Active Transient Yes

Product description

Puls Dimension C-series stands for cost optimization without compromising quality, reliability or performance.

CP10 is the second generation C-series 1-phase that sets new records by using the latest technology and sophisticated thermal design. With an efficiency of 95.5%, the power losses are very small and thus the width is reduced down to 39 mm. The efficiency is also very high at lower loads which is the normal operating condition. The mean value is on the whole 94.5% at 230 V ac.

Power boost of 20% enables higher current extraction without voltage drops. This is especially useful during start-ups and to bridge the current peaks in the application. The power reserve can be used continuously up to + 45°C and short periods from +45 to +60°C.

Short-circuit currents. CP10 can provide short circuit current which is 3 times the nominal current for at least 12 ms, which helps secondary fuses and achieve selectivity. For more information see under Sec, fuses.

Hiccup Plus

With Puls new short circuit technology ensures optimum protection. The unit leaves a very high short circuit that solves secondary fuses and provide sufficient starting current for example dc motors. If the output voltage falls below 26 V dc, a continuous current of 7 A is given for 2 seconds, then turn the assembly of the end to make a new restart attempt after about 18 seconds. This is done until the error has been corrected. This feature ensures a high short-circuit/overload current while avoiding a constant high current that can lead to thermal problems with cables and component damage.

More technical advantages. CP10 has active power factor correction (PFC) and actively current inrush protection that effectively reduces start currents which are ideal if several units are connected in the same phase or if the supply is current limited through example. AC UPS. The protection is always active, regardless of the temperature. DC-OK output, wide temperature range, a large number of approvals and transient filter which ensures operation in störrik electrical environment makes the unit suitable for virtually all installations.

 
For good cooling, we recommend a clearance of 40 mm over 20 mm below. We recommend 5 mm air gap to the sides. (15 mm on the sides of adjacent product is a heat source.)

 

Wiring

A: Primary side/control voltage

 

B: Secondary side. Output voltage

 

C: Potentiometer adjustable output voltage 48-56 V dc

 

D: DC OK LED. Lights when the voltage is 90% of the set value

 

E: DC-OK relay output. Closes when the output voltage is OK.

 

 

 

Sec. fuses

Breakers is the most common type of fuse for ac voltage but is also used for dc voltages. Power supply always has a current limitation compared with an electricity network which hampers tripping of a circuit breaker of the magnetic field. Greater consideration must be given to the cable diameter and cable lengths. This even if the power supply is able to deliver high short circuit currents. For long cables and/or thin cable area so the solution is electronic fuses.

 

Puls CP10.481 have high short-circuit currents which enables tripping within 10 ms of length and cable section is as below specification.

 

Safe tripping of breakers with different
cable lengths / diameters

Short circuit. Fig 3-2

 

0.75 mm2

1.0 mm2

1.5 mm2

2.5 mm2

C-2A

42 m

49 m

59 m

109 m

C-3A

13 m

24 m

28 m

42 m

 

 

 

 

Hiccup function. Fig 3-3

 

 

 

 

Description of Hiccupplus function

Thanks to the unique Pul Hiccupplus ensures a high short circuit current while avoiding the risk of overheated cables and damage to the connected loads. When a short circuit occurs following.

  1. High peak power that enables tripping in 12 ms Figure 3-2
  2. The unit leaves 7 A for 2 s.

After 2 seconds the unit shuts off, then try to restart every 18 seconds. If the fault is removed, the unit starts automatically, otherwise it will lose further 18 s. The operation does not burden the cabling and does not cause damage to the electronics.

 

Accessories

Related products

Articles Output voltage Input voltage AC Input voltage DC Clamp type Effect Output Current
48 V DC
100-240 V
110-150 V
Screw
120 W
2,5 A
48 V DC
100-240 V
110-150 V
Screw
260 W
5,4 A

Selected variant

Select a variant in the list

Contact us
Please contact us for more information.
Send e-mail
Do you need help?
Logo

Cookies on oem.ee

Cookies help us improve your experience with us, so in order to be able to handle login information, offer you personalised content and for basic functionality of this website, we use some cookies.

Functional cookies

These cookies are necessary for the website to work and can not be turned off in our systems. They are usually used only in response to actions you have taken in connection with a service request, for example when setting personal preferences, logging in or filling out a form.

Analytics cookies

These cookies allow us to count the number of visits and traffic sources so that we can measure and improve our website performance. They help us know which pages are more or less popular and how visitors navigate around the site. The information that these cookies collect is aggregated and therefore completely anonymous. If you do not allow these cookies, we do not know when you have visited our website.

Marketing cookies

These cookies can be added by our partners. They can use them to create a profile of you, based on your interests, to show you more relevant information. They do not store any personal information - only information about your browser and device. If you do not accept these cookies, you will have a more general and less customized user experience.